World’s largest lithium ion battery is down, again – pv magazine International

2022-05-14 22:31:45 By : Ms. yin li

The Moss Landing Energy Storage Facility Phase II in the United States set off fire alarms that activated a fault water suppression system, triggering a cascading set of events that resulted in roughly 10 battery packs melting down.

Image: Vistra Energy/Meranda Cohn

The Vistra Energy Moss Landing Energy Storage Facility Phase II set off fire alarms just after 8 p.m. (PST) on Feb. 13. Upon arrival, the local fire department found roughly 10 battery racks that were completely melted. The fire department representatives said that the fire was extinguished.

“We could confirm that it does have a fire suppression system, that the fire suppression system activated, and actually extinguished or cooled the batteries to the point where there wasn’t any flame or fire,” North County Fire District Chief, Joel Mendoza told local media outlets.

Vistra Energy later released an official statement on its website. The company says the onsite fire suppression systems performed as required, at least in the sense that the fire incident was isolated.

The California ISO energy website does show a drop in battery output at 7 p.m., local time. There is no indication this is related to the Moss Landing facility.

Vistra has suggested that the event might be a similar event to a September incident that took down the first phase of the facility. According to a statement from Vistra, that incident involved a cascading series of events which may have started with the failure of a ball bearing in a fan.

The suspected bearing failure is presumed to have set off the very early smoke detection apparatus (VESDA), which in turn armed the heat suppression system. Vistra stated that due to “failures of a small number of couplings on flexible hoses and pipes,” water sprayed directly onto additional battery racks, causing short circuiting and arcing, which damaged the batteries and made more smoke. The additional smoke set off more alarms and caused even more water to spray from the failed couplings.

While the cascading events following the smoke detection can be seen in the data, investigators have not explicitly determined what set off the smoke alarm in the first place.

Vistra says that they had been bringing the first facility back online incrementally, but have now decided to pause those activities. Pv magazine was not able to confirm whether any of the larger facility’s capacity has come back online.

This content is protected by copyright and may not be reused. If you want to cooperate with us and would like to reuse some of our content, please contact: editors@pv-magazine.com.

More articles from John Fitzgerald Weaver

Why does an electrical power facility use water fire suppression rather than halon?

Wasn’t halon phased out years ago?

Modern forms of Halon such as FM200 have been used widely in containerized battery storage facilities. Recent experience has shown that clean agent suppressants such as FM200 are ineffective in halting a thermal runaway fire in lithium ion batteries due to their inability to remove heat from the process. NFPA 855 recommends water-based fire suppression systems for lithium ion batteries.

Please be mindful of our community standards.

Your email address will not be published. Required fields are marked *

Save my name, email, and website in this browser for the next time I comment.

By submitting this form you agree to pv magazine using your data for the purposes of publishing your comment.

Your personal data will only be disclosed or otherwise transmitted to third parties for the purposes of spam filtering or if this is necessary for technical maintenance of the website. Any other transfer to third parties will not take place unless this is justified on the basis of applicable data protection regulations or if pv magazine is legally obliged to do so.

You may revoke this consent at any time with effect for the future, in which case your personal data will be deleted immediately. Otherwise, your data will be deleted if pv magazine has processed your request or the purpose of data storage is fulfilled.

Further information on data privacy can be found in our Data Protection Policy.

Legal Notice Terms and Conditions Privacy Policy © pv magazine 2022

This website uses cookies to anonymously count visitor numbers. View our privacy policy. ×

The cookie settings on this website are set to "allow cookies" to give you the best browsing experience possible. If you continue to use this website without changing your cookie settings or you click "Accept" below then you are consenting to this.